A safer kitchen starts with careful preparation, thorough grease removal and properly maintained exhaust equipment.

Cleaning safeguards

01

Inspection & qualified cleaning

NFPA 96 (2017) · 11.6.1 / 11.6.1.1

When inspection reveals grease contamination, affected exhaust surfaces must be cleaned by properly trained, qualified and certified persons acceptable to the authority having jurisdiction. Measure deposits to establish when cleaning is needed.

02

Grease-depth limits

NFPA 96 (2017) · 11.6.1.1.1 / 11.6.1.1.3 / 11.6.1.1.4

Clean hoods, grease-removal devices, ducts and other components to remove combustible deposits down to 50 μm (0.002 in.). The supplied code calls for cleaning at a measured depth of 2000 μm (0.078 in.), or 3175 μm (0.125 in.) in a fan housing.

03

Electrical lockout

NFPA 96 (2017) · 11.6.3

At the start of cleaning, lock out electrical switches that could be activated accidentally.

04

No flammable cleaning products

NFPA 96 (2017) · 11.6.6

Do not use flammable solvents or other flammable cleaning aids.

05

Service labels & records

NFPA 96 (2017) · 11.6.10 / 11.6.13

When an access panel is removed, affix a service-company label or tag near the affected panel identifying the company and inspection or cleaning date. Keep a certificate on the premises naming the servicing company, the person who performed the work and the inspection or cleaning date.

Filters & fan safety

Baffle filters & drainage

Baffle filters separate grease from exhaust air and drain it into a collection container, reducing fuel available for a fire. Clean them regularly and install the baffles vertically so grease can drain. Follow airflow-direction markings where provided.

Filter selection & installation

Use listed grease filters or listed grease-removal devices; the manual references UL 1046 for listed grease filters. Install filters at least 45° from horizontal, with vertical baffles. Steel is recommended; do not use aluminum filters over solid-fuel cooking. Caustic soda (lye) attacks aluminum.

Exhaust fans & grease containment

Use drains and collectors to contain grease dripping from fans. Protect fan discharge openings with an appropriate screen or guard against foreign objects and accidental contact. Provide proper hinged access for cleaning and inspection rather than improvised supports.

Fan suitability & discharge

Solid-fuel cooking requires fans designed for the higher temperatures involved. For outdoor utility-type centrifugal fans with horizontal discharge, the manual calls for an outlet duct connection directing exhaust upward.

Reference notes

Summarized from the supplied NFPA 96, 2017 edition, highlighted sections only; and the Kitchen Exhaust Cleaning and Certification Manual, © 2003 Phillip Ackland Holdings Ltd., Chapter 4 pages 13–14 and Chapter 6 page 4. These older references do not establish the currently adopted code. Applicable local requirements, manufacturer instructions and the authority having jurisdiction govern each installation; this summary is not a substitute for the complete standard or a professional inspection.

Keep your kitchen compliant, safe and spotless.